Estimate inverter continuous capacity, starting surge, battery current and approximate runtime. Read the complete guide →
Calculation formulas and assumptions
Minimum continuous inverter capacity = continuous AC load x (1 + headroom / 100). Estimated surge demand = continuous AC load + extra startup surge; headroom is not added to this surge estimate.
Continuous DC current = continuous AC load / (efficiency / 100) / minimum battery voltage. Surge DC current uses estimated surge demand in the same formula.
Usable nominal battery energy (Wh) = nominal voltage x battery capacity (Ah) x usable fraction / 100. Runtime (hours) = usable energy / (continuous AC load / (efficiency / 100) + additional DC watts).
Runtime assumes steady loads, constant efficiency and no charging input. Inverter standby draw, surge duration, battery voltage changes and BMS limits require separate review.
Planning estimates only: Verify inverter continuous and time-rated surge ratings, minimum operating battery voltage, BMS discharge limits, cable ampacity, fuse interrupt rating, and proper AC wiring. Surge allowance means additional load coinciding with running appliances. Runtime estimates assume steady consumption, nominal battery energy and constant efficiency.